● Battery is not used.
● 3 ½ digit LCD (2000-count).
● Backlight function.
● 15mA loop measurement which will not trip ELCBs.
● Convenient and easier for users to
measure the loop impedance directly without bypassing the wires.
● Wiring check function.
● Over temperature protection.
● Over voltage protection.
● Built-in voltmeter.
● Built-in earth tester.
● Built-in loop/psc tester.
● Safety standard :
EN 61010-1 CAT III 300V
EN 61326-1
Loop Impedance | |||
Range |
Measuring |
Nominal test current at 0 Ω external loop |
Accuracy |
20 Ω |
0.00~19.99 Ω |
23A / 40ms |
(2%rdg + 4dgt) |
200 Ω |
0.0~199.9 Ω |
2.3A / 40ms |
|
2000 Ω |
0~1999 Ω |
15mA / 400ms |
|
Prospective Short-circuit Current | |||
Range |
Measuring |
Nominal test current at 0 Ω external loop |
Accuracy |
20 KA |
0.00~4.00 KA |
23A / 40ms |
Consider accuracy of loop impedance |
2000 A |
0~1999 A |
23A / 40ms |
|
200 A |
0.0~199.9 A |
2.3A / 40ms |
|
Voltage Display | |||
Measuring range |
Accuracy |
Remark |
|
150~260 V |
(2%rdg + 4dgt) |
at 0 Ω external loop |
Voltage Display
Measuring range Accuracy Remark
150~260 V (2%rdg + 4dgt) at 0 Ω external loop
General
:Temperature 0 ~ 40 °C
:System voltage 230V
+13%
-15%
:System frequency 50Hz
:None Battery system voltage 150V ~ 260V
:Over Temperature Protection
When overheating,the ” ” symbol
will show on the LCD, and the 8025LP
stop measuring.
:Wiring check
P-E LEDs illuminate when the
wiring polarity of circuit under
P-N test is correct
N-E
LED is light when P and N are
reversed or the Earth is not
connected.
:15mA Loop measurement
Loop impedance 2000Ω range
measurement is carried out with low
test current (15mA).
The current will not cause tripping
out for ELCBs.