IR4056-20 DIGITAL INSULATION TESTER

$0.00

Product Highlights

Rated output voltage 50 V DC 125 V DC 250 V DC 500 V DC 1000 V DC
Effective maximum indicated value 100 MΩ 250 MΩ 500 MΩ 2000 MΩ 4000 MΩ
Accuracy 1st effective measuring range MΩ ±2 % rdg. ±2 dgt.
0.200 – 10.00
±2 % rdg. ±2 dgt.
0.200 – 25.0
±2 % rdg. ±2 dgt.
0.200 – 50.0
±2 % rdg. ±2 dgt.
0.200 – 500
±2 % rdg. ±2 dgt.
0.200 – 1000
Lower limit resistance 0.05 MΩ 0.125 MΩ 0.25 MΩ 0.5 MΩ 1 MΩ
Overload protection 600 V AC (10s) 660 V AC (10s)
DC voltage measurement 4.2 V (0.001 V resolution) to 600 V (1 V resolution), 4 ranges,
Accuracy: ±1.3 % rdg. ±4 dgt., Input resistance: 100 kΩ or higher
AC voltage measurement 420 V (0.1 V resolution) / 600 V (1 V resolution), 2 ranges, 50/60 Hz,
Accuracy: ±2.3% rdg. ±8 dgt., Input resistance: 100 kΩ or higher, Average rectifier
Low resistance measurement For checking the continuity of ground wiring, 10 Ω (0.01 Ω resolution) to 1000 Ω (1 Ω resolution), 3 ranges, Basic accuracy: ±3 % rdg. ±2 dgt., testing current 200 mA or more (at 6 Ω or less)
Display Semi-transmissive FSTN LCD with back lighting, bar-graph indicator

In stock

Buy Now
Compare
in stock

Description

Hioki insulation testers or megohmmeters feature all-in-one designs including built-in rugged cases and test lead storage compartments. The IR4056 is a 5-range, 50V to 1000V digital insulation resistance tester with efficient functions and features to help shorten work time associated with field insulation testing. CAT III 600 V Excluding IR4056-21

Rated output voltage 50 V DC 125 V DC 250 V DC 500 V DC 1000 V DC
Effective maximum indicated value 100 MΩ 250 MΩ 500 MΩ 2000 MΩ 4000 MΩ
Accuracy 1st effective measuring range MΩ ±2 % rdg. ±2 dgt.
0.200 – 10.00
±2 % rdg. ±2 dgt.
0.200 – 25.0
±2 % rdg. ±2 dgt.
0.200 – 50.0
±2 % rdg. ±2 dgt.
0.200 – 500
±2 % rdg. ±2 dgt.
0.200 – 1000
Lower limit resistance 0.05 MΩ 0.125 MΩ 0.25 MΩ 0.5 MΩ 1 MΩ
Overload protection 600 V AC (10s) 660 V AC (10s)
DC voltage measurement 4.2 V (0.001 V resolution) to 600 V (1 V resolution), 4 ranges,
Accuracy: ±1.3 % rdg. ±4 dgt., Input resistance: 100 kΩ or higher
AC voltage measurement 420 V (0.1 V resolution) / 600 V (1 V resolution), 2 ranges, 50/60 Hz,
Accuracy: ±2.3% rdg. ±8 dgt., Input resistance: 100 kΩ or higher, Average rectifier
Low resistance measurement For checking the continuity of ground wiring, 10 Ω (0.01 Ω resolution) to 1000 Ω (1 Ω resolution), 3 ranges, Basic accuracy: ±3 % rdg. ±2 dgt., testing current 200 mA or more (at 6 Ω or less)
Display Semi-transmissive FSTN LCD with back lighting, bar-graph indicator